A lot of Testing Power in the hands of Electrical Installation Professionals!
KYORITSU 6516BT Multi Function Tester
DISPLAY | Color LCD 3.5 inches dot matrix. |
ATT | Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs. With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines). |
LOOP | High test current range of 2Ω with 0.001Ω resolution. Zs Limit compares the values required by Electrical Installations Standard with measured results. |
RCD | Type AC, A, F, B(General & Selective), EV and Variable RCDs. Single and Auto test, Ramp test and Contact voltage. |
EARTH | Earth resistance test 2 and 3 wires with all accessories included. |
INSULATION | Resistance test 100, 250, 500 & 1000V with auto discharge voltage. |
CONTINUITY | Continuity test at 200mA or 15mA with selectable buzzer for fast judgment. |
PHASE ROTATION | On 3-phase lines with clear indication of the sequence on the display. |
VOLTS | TRMS Voltage measurements 2-600V, Mains Frequency. |
HELP | Display shows how to connect the instrument according to the function selected. |
SPD | Surge Protection Device test, for SPD that uses varistor. |
PAT | Portable Appliance Tester function, for Insulation and Protective conductor resistance test |
Bluetooth | Communication by “KEW CONNECT” |
SAFETY | IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10. |
Insulation resistance | SPD(Varistor) | ||||
---|---|---|---|---|---|
Test voltage |
100V | 250V | 500V | 1000V | Max.1000V |
Measuring ranges |
2.000/20.00/200.0MΩ (Auto-ranging) |
20.00/200.0/1000MΩ (Auto-ranging) |
20.00/200.0/2000MΩ (Auto-ranging) |
0-1000V (goes up by 1V) |
|
Accuracy | ±2%rdg±6dgt (2.000/20.00MΩ) ±5%rdg±6dgt (200.0MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (1000MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (2000MΩ) |
±5%rdg±5dgt | |
Rated current |
1.0-1.2mA @0.1MΩ |
1.0-1.2mA @0.25MΩ |
1.0-1.2mA @0.5MΩ |
1.0-1.2mA @1MΩ |
‐ |
Short circuit current | 1.5mA max |
Loop impedance | |||||
---|---|---|---|---|---|
Function | LOOP ATT | LOOP HIGH | |||
L-PE/L-N (3wire) |
L-PE (2wire) |
L-PE (0.01ΩRes) |
L-PE (0.001ΩRes) High test current(25A) |
L-N/L-L | |
Rated voltage |
100-260V (50/60Hz) |
48-260V (50/60Hz) |
48-260V (50/60Hz) |
100-260V (50/60Hz) |
48-500V (50/60Hz) |
Impedance range |
20.00/200.0/2000Ω (Auto-ranging) |
20.00/200.0/ 2000Ω (Auto-ranging) |
2.000Ω | 20.00Ω | |
Accuracy | ±3%rdg±6dgt | ±3%rdg±10dgt | ±3%rdg±4dgt | ±3%rdg±25mΩ | ±3%rdg±4dgt |
Nominal test current at 0Ω external loop: Magnitude/ Duration at 230V |
L-N:6A/60ms N-PE:10mA |
L-PE:15mA | 20Ω: 6A/20ms 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms | 6A/20ms |
PSC/PFC | |||||
---|---|---|---|---|---|
Range | 2000A/20kA (L-N(PSC)/ L-PE(PFC)) |
2000A/20kA (PFC) |
2000A/20kA (PFC) |
2000A/50kA (PFC) |
2000A/20kA (PSC) |
Accuracy | PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification |
RCD | ||||||||
---|---|---|---|---|---|---|---|---|
Rated voltage | 100-260V(50/60Hz) | |||||||
Function | x1/2, x1,x5,Ramp,Auto,Uc | |||||||
6/10/30/100/300/500/1000mA/variable | ||||||||
RCD type | AC(G/S) | A(G/S) | F(G/S) | B(G/S) | EV | |||
Trip current setting |
x1/2, x1,Uc |
10/30/100/300/ 500/1000mA(G) 10/30/100/ 300/500(S) |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA(x1 only) | ||
x5 | 10/30/100mA | 10/30/100mA | 10/30/100mA | 10/30mA | – | |||
Ramp | 10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA | |||
Accuracy | ||||||||
Trip current |
x1/2 | -8% – -2% | -10% – 0% | -10% – 0% | -10% – 0% | – | ||
x1 | +2% – +8% | 0% – +10% | 0% – +10% | 0% – +10% | 0% – +10% | |||
x5 | +2% – +8% | 0% – +10% | 0% – +10% | 0% – +10% | – | |||
Ramp | -4% – +4% | -10% – +10% | -10% – +10% | -10% – +10% | -10% – +10% | |||
Trip time |
x1/2 | 2000ms(G/S):±1%rdg±2ms | – | |||||
x1 | 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms | 10.5s:±1%±2㎳ | ||||||
x5 | 410ms(G/S):±1%rdg±2ms | – |
Continuity | ||||
---|---|---|---|---|
Range | 20.00/200.0/2000Ω (Auto-ranging) | |||
Open circuit voltage(DC) | 7-14V | |||
Measuring current | 200mA | >200mA or more(2Ω or less) | ||
15mA | 15mA±3mA(short-circuit) | |||
Accuracy | ±2%rdg±8dgt |
Volts | ||||
---|---|---|---|---|
Range | 300.0/600V(Auto-ranging) | |||
Measuring ranges | Volts | 2-600V | ||
Frequency | 45-65Hz | |||
Accuracy | Volts | ±2%rdg±4dgt | ||
Frequency | ±0.5%rdg±2dgt |
Earth | ||||
---|---|---|---|---|
Range | 20.00/200.0/2000Ω(Auto-ranging) | |||
Accuracy | ±2%rdg±0.08Ω(20.00Ω) ±2%rdg±3dgt(200.0/2000Ω) |
Applicable standards | IEC 61010-1 CAT IV 300V ,CAT III 600 V Pollution degree 2 IEC 61010-2-034 IEC 61557-1,2,3,4,5,6,7,10 IEC 60529(IP40) IEC 61326(EMC) |
---|---|
Power source | LR6 (AA) (1.5V) ×8 |
Communication interface | USB |
Dimensions / Weight | 136(L) × 235(W) × 114(D) mm / Approx. 1300g (including batteries) |
Included Accessories | Main test lead※1 7281(Test leads with remote control switch) 7246(Distribution board test lead) 7228A(Earth resistance test leads) 8041(Auxiliary earth spikes[2 spikes/1 set]) 9084(Soft case) 9142(Carrying case) 9151(Shoulder strap) 9199(Shoulder pad) 8212-USB(USB adaptor with “KEW Report(Software)”) LR6(AA) × 8, Instruction manual, Calibration certificate |
Optional Accessories | 8259(Adapter for measurement terminal) 7272(Precision measurement Cord set) 8017A(Extension prod long) |